1 .. 43 44 45 46 47 48 49 50 51 52 53 .. 66
6. CAPACITY TABLES
DATA G10
HEAT SOURCE UNITS
2 - 394
WY
6-3-3. How to obtain the equivalent piping length
1
PQHY-P200YHM
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.35 x number of bends in the piping) m
2
PQHY-P250,
300YHM
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.42 x number of bends in the piping) m
3
PQHY-P400, 450, 500, 550, 600, 650YSHM
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 x number of bends in the piping) m
4
PQHY-P700, 750, 800YSHM
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.70 x number of bends in the piping) m
5
PQHY-P850,
900YSHM
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.80 x number of bends in the piping) m