1. SPECIFICATIONS
DATA G10
OUTDOOR UNITS
2 - 198
HP
Model
PUHY-HP500YSHM-A(-BS)
Power source
3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity
*1
kW
56.0
(Nominal)
*1
kcal / h
48,200
*1
BTU / h
191,100
Power input
kW
18.16
Current input
A
30.6-29.1-28.0
COP
kW / kW
3.08
Temp. range of
Indoor
W.
B.
15 to 24degC(59 to 75degF)
cooling
Outdoor
D.B.
-5 to 43degC(23 to 109degF)
Heating capacity
*2
kW
63.0
(Nominal)
*2
kcal / h
54,200
*2
BTU / h
215,000
Power input
kW
18.04
Current input
A
30.4-28.9-27.8
COP
kW / kW
3.49
Temp. range of
Indoor
D.
B.
15 to 27degC(59 to 81degF)
heating
Outdoor
W.B.
-25 to 15.5degC(-13 to 60degF)
Indoor unit
Total capacity
50 to 130 % of outdoor unit capacity
connectable
Model / Quantity
P15 to P250 / 1 to 43
Sound pressure level (measured in anechoic room)
dB <A>
60
Refrigerant
Liquid pipe
mm(in.)
15.88(5/8) Brazed
piping diameter
Gas pipe
mm(in.
)
28.58(1-1/8) Brazed
Set Model
Model
PUHY-HP250YHM-A(-BS)
PUHY-HP250YHM-A(-BS)
FAN
Type x Quantity
Propeller fan x 1
Propeller fan x 1
Air flow rate
m
3
/ min
225
225
L/s
3,750
3,750
cfm
7,945
7,945
Control, Driving mechanism
Inverter-control,Direct-driven by motor
Inverter-control,Direct-driven by motor
Motor output
kW
0.92 x 1
0.92 x 1
*3
External static press.
0 Pa (0 mmH
2
O)
0 Pa (0 mmH
2
O)
Compressor
Type x Quantity
Inverter scroll hermetic compressor
Inverter scroll hermetic compressor
Manufacture
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method
Inverter
Inverter
Motor output
kW
6.7
6.7
Case heater
kW
0.045
0.045
Lubricant
MEL32
MEL32
External finish
Pre-coated galvanized steel sheets
Pre-coated galvanized steel sheets
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
External dimension HxWxD
mm
1,650 x 920 x 760
1,650 x 920 x 760
in.
65 x 36-1/4 x 29-15/16
65 x 36-1/4 x 29-15/16
Protection devices
High pressure protection
High pressure sensor, High pressure switch at 4.15MPa (601
psi)
High pressure sensor, High pressure switch at 4.15MPa (601
psi)
Inverter circuit (COMP.
/ FAN)
Over-heat protection,Over-current protection
Over-heat protection,Over-current protection
Compressor
Over-heat protection
Over-heat protection
Fan motor
Thermal switch
Thermal switch
Refrigerant
Type x original charge
R410A x 9.0kg (20lbs)
R410A x 9.0kg (20lbs)
Control
LEV and HIC circuit
Net weight
kg(lbs)
220(486)
220(486)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Pipe between unit and
Liquid pipe
mm(in.)
9.52(3/8) Brazed
9.52(3/8) Brazed
disrributor
Gas pipe
mm(in.
)
22.2(7/8) Brazed
22.2(7/8) Brazed
Defrosting method
Auto-defrost mode (Reversed refrigerant circle)
Drawing
External
WKB94R111
Wiring
WKE79B230
WKE79B230
Standard attachment
Document
Installation Manual
Accessory
Refrigerant conn. pipe
Optional parts
Outdoor Twinning kit: CMY-Y100VBK2/3
Joint: CMY-Y102SS/LS-G2,CMY-Y202S-G2
Header: CMY-Y104/108/1010-G
Remark
* Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
* Due to continuing improvement, above specifications may be subject to change without notice.
Note :
*1 Nominal cooling conditions (subject to JIS B8615-2)
*2 Nominal heating conditions (subject to JIS B8615-2)
Unit converter
Indoor :
27degCDB/19degCWB
(81degFDB/66degFWB)
20degCDB
(68degFDB)
kcal
=kW x 860
BTU/h
=kW x 3,412
Outdoor :
35degCDB
(95degFDB)
7degCDB/6degCWB
(45degFDB/43degFWB)
cfm
=m
3
/min x 35.31
lbs
=kg / 0.4536
Pipe length :
7.5m(24-9/16ft.)
7.5m(24-9/16ft.)
Level difference :
0m(0ft.
)
0m(0ft.)
*The specification data is
*3 External static pressure option is available (30Pa, 60Pa / 3.1mmH
2
O, 6.1mmH
2
O).
subject to rounding variation.