2 - 117
1. SPECIFICATIONS
DATA G10
OUTDOOR UNITS
Y (HIGH COP)
Model
PUHY-EP300YJM-A(-BS)
Power source
3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity
*1
kW
33.5
(Nominal)
*1
kcal/h
28,800
*1
BTU/h
114,300
Power input
kW
8.03
Current input
A
13.5-12.8-12.4
COP
kW/kW
4.17
Temp.
range of
Indoor
W.
B.
15.0~24.0°C(59~75°F)
cooling
Outdoor
D.B.
-5.0~46.0°C(23~115°F)
Heating capacity
*2
kW
37.5
(Nominal)
*2
kcal/h
32,300
*2
BTU/h
128,000
Power input
kW
8.37
Current input
A
14.1-13.4-12.9
COP
kW/kW
4.48
Temp.
range of
Indoor
D.
B.
15.0~27.0°C(59~81°F)
heating
Outdoor
W.B.
-20.0~15.5°C(-4~60°F)
Indoor unit
Total capacity
50~130 % of outdoor unit capacity
connectable
Model/Quantity
P15~P250/1~26
Sound pressure level (measured in anechoic room)
dB <A>
61
Power pressure level (measured in anechoic room)
dB <A>
81
Refrigerant
Liquid pipe
mm (in.
)
9.52(3/8) Brazed (12.7(1/2) Brazed,total length >= 40m)
piping diameter
Gas pipe
mm (in.
)
22.2(7/8) Brazed
FAN
Type x Quantity
Propeller fan x 2
Air flow rate
m
3
/min
370
L/s
6,167
cfm
13,065
Control, Driving mechanism
Inverter-control, Direct-driven by motor
Motor output
kW
0.46 x 2
*3
External static press.
0 Pa (0 mmH
2
O)
Compressor
Type x Quantity
Inverter scroll hermetic compressor
Manufacture
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method
Inverter
Motor output
kW
7.7
Case heater
kW
0.045
Lubricant
MEL32
External finish
Pre-coated galvanized steel sheets (+powder coating for -BS
type)
<MUNSELL 5Y 8/1 or similar>
External dimension HxWxD
mm
1,710(1,650 without legs) x 1,750 x 760
in.
67-3/8(65 without legs) x 68-15/16 x 29-15/16
Protection devices
High pressure protection
High pressure sensor, High pressure switch at 4.15MPa (601
psi)
Inverter circuit (COMP.
/FAN)
Over-heat protection, Over-current protection
Compressor
Over-heat protection
Fan motor
Thermal switch
Refrigerant
Type x original charge
R410A x 11.8kg (27lbs)
Control
LEV and HIC circuit
Net weight
kg (lbs)
290(640)
Heat exchanger
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
Drawing
External
WKD94G077
Wiring
KE94C450
Standard attachment
Document
Installation Manual
Accessory
Refrigerant conn. pipe
Optional parts
Joint: CMY-Y102SS/LS-G2
Header: CMY-Y104/108/1010-G
Remarks
Details on foundation work, duct work, insulation work, electri-
cal wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
Due to continuing improvement, above specifications may be
subject to change without notice.
Notes :
Unit converter
1.Nominal cooling conditions(subject to JIS B8615-2)
Indoor:27°CDB/19°CWB(81°FDB/66°FWB), Outdoor:35°CDB(95°FDB)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
2.Nominal heating conditions(subject to JIS B8615-2)
Indoor:20°CDB(68°FDB), Outdoor:7°CDB/6°CWB(45°FDB/43°FWB)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
3.External static pressure option is available (30Pa, 60Pa/3.1mmH
2
O, 6.1mmH
2
O).
kcal
=kW x 860
BTU/h
=kW x 3,412
cfm
=m
3
/min x 35.31
lbs
=kg/0.4536
*Above specification data is
subject to rounding variation.