1. SPECIFICATIONS
DATA G10
OUTDOOR UNITS
2 - 116
Y (
H
IG
H
COP
)
I.
Y (High COP) SERIES
1. SPECIFICATIONS
Model
PUHY-EP200YJM-A(-BS)
PUHY-EP250YJM-A(-BS)
Power source
3-phase 4-wire 380-400-415V 50/60Hz
3-phase 4-wire 380-400-415V 50/60Hz
Cooling capacity
*1
kW
22.4
28.0
(Nominal)
*1
kcal/h
19,300
24,100
*1
BTU/h
76,400
95,500
Power input
kW
5.09
6.73
Current input
A
8.5-8.1-7.8
11.3-10.7-10.4
COP
kW/kW
4.40
4.16
Temp. range of
Indoor
W.
B.
15.0~24.0°C(59~75°F)
15.0~24.0°C(59~75°F)
cooling
Outdoor
D.B.
-5.0~46.0°C(23~115°F)
-5.0~46.0°C(23~115°F)
Heating capacity
*2
kW
25.0
31.5
(Nominal)
*2
kcal/h
21,500
27,100
*2
BTU/h
85,300
107,500
Power input
kW
5.54
7.15
Current input
A
9.3-8.8-8.5
12.0-11.4-11.0
COP
kW/kW
4.51
4.40
Temp. range of
Indoor
D.
B.
15.0~27.0°C(59~81°F)
15.0~27.0°C(59~81°F)
heating
Outdoor
W.B.
-20.0~15.5°C(-4~60°F)
-20.0~15.5°C(-4~60°F)
Indoor unit
Total capacity
50~130 % of outdoor unit capacity
50~130 % of outdoor unit capacity
connectable
Model/Quantity
P15~P250/1~17
P15~P250/1~21
Sound pressure level (measured in anechoic room)
dB <A>
57
60
Power pressure level (measured in anechoic room)
dB <A>
77
80
Refrigerant
Liquid pipe
mm (in.)
9.52(3/8) Brazed
9.52(3/8) Brazed (12.7(1/2) Brazed,total length >= 90m)
piping diameter
Gas pipe
mm (in.)
19.05(3/4) Brazed
22.2(7/8) Brazed
FAN
Type x Quantity
Propeller fan x 1
Propeller fan x 1
Air flow rate
m
3
/min
170
210
L/s
2,833
3,500
cfm
6,003
7,415
Control, Driving mechanism
Inverter-control, Direct-driven by motor
Inverter-control, Direct-driven by motor
Motor output
kW
0.46 x 1
0.46 x 1
*3
External static press.
0 Pa (0 mmH
2
O)
0 Pa (0 mmH
2
O)
Compressor
Type x Quantity
Inverter scroll hermetic compressor
Inverter scroll hermetic compressor
Manufacture
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method
Inverter
Inverter
Motor output
kW
5.4
6.8
Case heater
kW
0.035
0.045
Lubricant
MEL32
MEL32
External finish
Pre-coated galvanized steel sheets (+powder coating for -BS
type)
Pre-coated galvanized steel sheets (+powder coating for -BS
type)
<MUNSELL 5Y 8/1 or similar>
<MUNSELL 5Y 8/1 or similar>
External dimension HxWxD
mm
1,710(1,650 without legs) x 920 x 760
1,710(1,650 without legs) x 1,220 x 760
in.
67-3/8(65 without legs) x 36-1/4 x 29-15/16
67-3/8(65 without legs) x 48-1/16 x 29-15/16
Protection devices
High pressure protection
High pressure sensor, High pressure switch at 4.15MPa (601
psi)
High pressure sensor, High pressure switch at 4.15MPa (601
psi)
Inverter circuit (COMP./FAN)
Over-heat protection, Over-current protection
Over-heat protection, Over-current protection
Compressor
Over-heat protection
Over-heat protection
Fan motor
Thermal switch
Thermal switch
Refrigerant
Type x original charge
R410A x 8.0kg (18lbs)
R410A x 11.5kg (26lbs)
Control
LEV and HIC circuit
LEV and HIC circuit
Net weight
kg (lbs)
200(441)
250(552)
Heat exchanger
Salt-resistant cross fin & copper tube
Salt-resistant cross fin & copper tube
HIC circuit (HIC: Heat Inter-Changer)
Copper pipe,tube-in-tube structure
Copper pipe,tube-in-tube structure
Defrosting method
Auto-defrost mode (Reversed refrigerant cycle)
Auto-defrost mode (Reversed refrigerant cycle)
Drawing
External
WKD94G075
WKD94G076
Wiring
KE94C449
KE94C449
Standard attachment
Document
Installation Manual
Installation Manual
Accessory
Refrigerant conn. pipe
Refrigerant conn. pipe
Optional parts
Joint: CMY-Y102SS-G2
Joint: CMY-Y102SS/LS-G2
Header: CMY-Y104/108/1010-G
Header: CMY-Y104/108/1010-G
Remarks
Details on foundation work, duct work, insulation work, electri-
cal wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
Due to continuing improvement, above specifications may be
subject to change without notice.
Details on foundation work, duct work, insulation work, electri-
cal wiring, power source switch, and other items shall be re-
ferred to the Installation Manual.
Due to continuing improvement, above specifications may be
subject to change without notice.
Notes :
Unit converter
1.Nominal cooling conditions(subject to JIS B8615-2)
Indoor:27°CDB/19°CWB(81°FDB/66°FWB), Outdoor:35°CDB(95°FDB)
Pipe length:7.5m(24-9/16ft.
), Level difference:0m(0ft.)
2.Nominal heating conditions(subject to JIS B8615-2)
Indoor:20°CDB(68°FDB), Outdoor:7°CDB/6°CWB(45°FDB/43°FWB)
Pipe length:7.5m(24-9/16ft.
), Level difference:0m(0ft.)
3.External static pressure option is available (30Pa, 60Pa/3.1mmH
2
O, 6.1mmH
2
O).
kcal
=kW x 860
BTU/h
=kW x 3,412
cfm
=m
3
/min x 35.31
lbs
=kg/0.4536
*Above specification data is
subject to rounding variation.