2. EXTERNAL DIMENSIONS
DATA G10
OUTDOOR UNITS
2 - 60
Y
ø34.93
ø19.05
CMY
-Y200VBK2
PUHY
-P700YSJM-A1(-BS)
PUHY
-P400YJM-A(-BS)
PUHY
-P300YJM-A(-BS)
PUHY
-P300YJM-A(-BS)
PUHY
-P350YJM-A(-BS)
PUHY
-P650YSJM-A(-BS)
ø28.58
ø15.88
CMY
-Y100VBK2/3
PUHY
-P250YJM-A(-BS)
PUHY
-P350YJM-A(-BS)
PUHY
-P600YSJM-A(-BS)
b
a
Gas
Liquid
Outdoor unit 2
Outdoor unit 1
Indoor unit~T
winning pipe
Outdoor T
winning
Kit(optional
parts)
Component unit name
Package unit name
T
winning pipe connection size
P400
P350
T
winning pipe~Outdoor unit
d or f
c or e
Gas
Liquid
P250
P300
Unit model
Detachable leg
Note 2*
ø28.58
ø15.88
ø12.7
ø28.58
ø12.7
ø22.2
ø22.2
ø9.52
Front view
Left view
T
o indoor unit
Liquid T
winning
pipe<optional
parts>
Gas T
winning
pipe<optional
parts>
T
o indoor unit
d
c
f
e
b
a
Intake
air
Outdoor unit 2
Outdoor unit 1
Discharge air
Intake
air
Intake
air
30
1710
1650
(60)
920
1220
760
Note 1.Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
     2.The detachable leg can be removed at site.
     3.T
winning pipes should not be tilted more than 15 degrees from the horizontal plane.  
       Be sure to see the Installation Manual for details of
T
winning pipe installation.
     4.The pipe section before the
T
winning pipe (sections "a" and "b" in the figure) must have at least 500mm of straight sect
ion
       (*including the straight pipe that is supplied with the
T
winning pipe).
     5.Only use the
T
winning pipe by Mitsubishi (optional parts).
PUHY
-P600, 650, 700YSJM-A(1)(-BS)
Unit : mm