2 - 53
2. EXTERNAL DIMENSIONS
DATA G10
OUTDOOR UNITS
Y
2. EXTERNAL DIMENSIONS
For transmission cables
For wires
For pipes
Specifications
Usage
NO.
<Accessories>
Connecting pipe
<Gas>
•
Elbow(ID
ø
19.05XODø19.05)···
P200
•Elbow(IDø25.4XODø25.4)··
····
·P250,P300
•
Pipe (ID
ø25.4XODø22.2)········
P250,P300
Note1.
Please refer to the next page for information
regarding necessary spacing around the
unit and foundation work.
2.
The detachable leg can be removed at site.
At brazing of pipes,wrap the refrigerant service valve
with wet cloth and keep the temperature of
refrigerant service valve under 120°C
3.
1pc.
1pc.
1pc.
<Liquid>
•
Pipe (IDø9.52XODø9.52)··
·····
·P200,P250
•
Pipe (IDø12.7XODø12.7)
········
P300
•
Pipe (IDø12.7XODø9.52)
········
P300
1pc.
1pc.
1pc.
1
2
3
4
5
6
Front through hole
Bottom through hole
Front through hole
Front through hole
Bottom through hole
Front through hole
102X72 Knockout hole
150X92 Knockout hole
ø65 or ø40 Knockout hole
ø52 or ø27 Knockout hole
ø52 Knockout hole
ø34 Knockout hole
2X5-ø4.6 Hole
(Make hole at the plastic fan guard
for snow hood attachment)
150
150
150
150
80
18
884
18
760
920
<Snow hood attachment hole>
T
op view
1710
1410
1650
240
Intake
air
Service
panel
Control box
Intake
air
(60)
72
90
102
98
204
251
132
88
2X2-14X20 Oval hole
(front and back,2 points)
Note 2*
Detachable leg
6
4
3
1
Front view
221
150
83
251
186
145
760
18
18
86
80
80
92
Refrigerant service
valve <gas>
5
2
131
C
Refrigerant service
valve <liquid>
(Mounting pitch)
Bottom view
(Mounting pitch)
(760)
724(721
~
727)
Discharge air
Intake
air
Refrigerant service
valve <gas>
Refrigerant service
valve <liquid>
A
B
(60)
55
60
25
760
25
55
60
54
Left side view
Connecting pipe specifications
150
145
C
170
172
143
142
B
A
Gas
Liquid
PUHY
-P300YJM
PUHY
-P250YJM
PUHY
-P200YJM
Model
Position dimensions
for the refrigerant
service valve
Connection specifications for
the refrigerant service valve*1
Gas
Liquid
ø19.05 Brazed
ø22.2 Brazed
ø9.52 Brazed
ø9.52 Brazed
(ø12.7 Brazed) *3
ø9.52 Brazed
(ø12.7 Brazed)
*2 *4
*1 Connect by using the connecting pipes (for bottom piping and front piping)
that are supplied.
*2 Indicates dimensions and connection specifications in the case the unit is
used in combination with other outdoor units.
*3 T
otal
length
>=
90m
*4 T
otal
length
>=
40m
PUHY
-P200,250,300YJM-A(-BS)
Unit : mm