2 - 41
Y
MEE15K022
2. EXTERNAL DIMENSIONS
YKB/YLM 2nd
PUHY
-P800, 850YSKB-A1(-BS)
Unit : mm
740
1650
(60)
1710
30
1220
1750
Intake
air
Outdoor unit 2
Discharge air
T
o indoor unit
Gas
T
winning pipe<optional parts>
Liquid
T
winning pipe<optional parts>
T
o indoor unit
Left view
Front view
Intake
air
Intake
air
Outdoor unit 1
Detachable leg
Note 5*
a
b
f
e
c
d
T
winning pipe~Outdoor unit
d or f
c or e
Gas
Liquid
Unit model
ø12.7
T
winning pipe connection size
Package unit name
Component unit name
Outdoor T
winning
Kit(optionalparts)
Outdoor unit 1
Outdoor unit 2
Indoor unit~T
winning pipe
Liquid
Gas
a
b
CMY
-Y200VBK2
ø34.93
PUHY
-P350YKB-A1(-BS)
PUHY
-P800YSKB-A1(-BS)
ø19.05
PUHY
-P450YKB-A1(-BS)
P350
PUHY
-P400YKB-A1(-BS)
PUHY
-P850YSKB-A1(-BS)
PUHY
-P450YKB-A1(-BS)
P450
ø28.58
ø15.88
P400
Note
1.
Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2.
T
winning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of
T
winning pipe installation.
3.
The pipe section before the
T
winning pipe (sections "a" and "b" in the figure) must have
4.
Only use the
T
winning pipe by Mitsubishi (optional parts).
5.
The detachable leg can be removed at site.
at least 500mm of straight section (*including the straight pipe that is supplied with the
T
winning pipe).
ø41.28